WRITE LIST REGISTER:
ADDRESS DESCRIPTION MIN-MAX LIMITS
39 Cooling setpoint -200 - 260 [°C]
40 Cooling setpoint band 10 - 200 [°C]
41 Heating setpoint 250 - 650 [°C]
42 Heating setpoint band 10 - 200 [°C]
43 Setpoint correction 0 - 3
44 Cooling setpoint 1 -200 - 260 [°C]
45 External AT in cool mode 1 400 - 500 [°C]
46 Cooling setpoint 2 -200 - 260 [°C]
47 External AT in cool mode 2 -400 - 500 [°C]
48 Heating setpoint 1 250 - 650 [°C]
49 External AT in heat mode 1 -400 - 500 [°C]
50 Heating setpoint 2 250 - 650 [°C]
51 External AT in heat mode 2 -400 - 500 [°C]
52 Domestic water setpoint -250 - 650 [°C]
53 Domestic water band 10 - 200 [°C]
54 Power percentage requested from the thermostat 0 - 100 [%]
55 PWD_SET_VMF -32768 - 32767
56 Remote probe DHW -32768 ÷ 32767
LIST OF EXCEPTIONS:
The error codes highlighted by the Modu Control card are shown below:
!
EXCEPTION DESCRIPTION
The requested function code is not managed by the card.
The data request contains a reference to an address that is not
available on the card.
The data write request contains a value that is out of range,
so writing is not allowed.
COMANDI SCRITTURA DISPONIBILI
Preset Single Register
Preset Multiple Registers