57
GB
6343841_00 / Ver - 4.20
Supervisor write enabled
Index - String
MIN
value
MAX
value
Parameter function
0 1 This parameter enables the write commands for the supervisor; this enablement is set
on the basis of the value selected for this parameter:
0 = write command disabled
1 = write command enabled
Remember that the read commands are always active.
Air temperature limit 1
(*)
Index - String
MIN
value
MAX
value
Parameter function
j
-25°C 45°C This parameter indicates the external air temperature at which the machine can produce
its maximum water value (this value is specified in parameter P - St1).
Water temperature limit 1
(*)
Index - String
MIN
value
MAX
value
Parameter function
j
0°C 70°C This parameter indicates the maximum temperature of the water produced, in line with
the outside air temperature specified in parameter O - LA1.
Air temperature limit 2
(*)
Index - String
MIN
value
MAX
value
Parameter function
j
-25°C 45°C This parameter indicates the external air temperature at which the machine can produce
its maximum water value (this value is specified in parameter R - St2).
Water temperature limit 2
(*)
Index - String
MIN
value
MAX
value
Parameter function
j
0°C 70°C This parameter indicates the maximum temperature of the water produced, in line with
the outside air temperature specified in parameter Q - LA2.
(*)
these parameters describe the operating limits (in heat mode) of the compressor, beyond which it is automatically
switched off and, when necessary, heat operation is guaranteed by the supplementary electric heater;
Maximum heating set point
Index - String
MIN
value
MAX
value
Parameter function
j
15°C 65°C This parameter indicates the maximum temperature of the water produced by the unit in
heat mode.
j
j
j
Parameters only visible in heat pump models
j
j
j
Parameters only visible in models set for
hot domestic water production
Parameters only visible in the models with DCP installed
Parameters only visible in bicompressor models
Parameters only visible in the models with inverter compressor

Other manuals for AERMEC MODUCONTROL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC MODUCONTROL and is the answer not in the manual?

AERMEC MODUCONTROL Specifications

General IconGeneral
BrandAERMEC
ModelMODUCONTROL
CategoryControl Unit
LanguageEnglish

Related product manuals