58
GB
6343841_00 / Ver - 4.20
INSTALLER 2 menu
To access the INSTALLER_2 menu, follow the same procedure described for the INSTALLER menu; the only difference
is the value of the password, which is 31.
R
Fig.9a Fig.10a
R
Setting operational parameters (installer level)
PASSWORD = 031
WARNING The following parameters
must only be modifi ed by qualifi ed
personnel authorised to install the
unit.
j
j
j
Parameters only visible in heat pump models
j
j
j
Parameters only visible in models set for
hot domestic water production
Parameters only visible in the models with DCP installed
Parameters only visible in bicompressor models
Parameters only visible in the models with inverter compressor
Threshold for reactivation after shutdown force off
Index - String
MIN
value
MAX
value
Parameter function
0 °C 30 °C
If the parameter value rin = 4 (parameter 8 of the Installer menu), then this is a probe
storage system, this parameter indicates how much lower the threshold of force off so
as to prevent the compressor is reactivated after the intervention of ForceOff dynamic
extinguished soon after.
Configuration of the heating cable (ANK only)
Index - String
MIN
value
MAX
value
Parameter function
02
Setting the output to which the heating cable is connected:
0- no heating cable
1- heating cable on the CPA output
(the parameter (0) of the menu with password=72 “according to CP must be 0”
2- heating cable on the VGC output if not used (the configuration of the dip switches must
be: DIP1 = ON, DIP2=ON, DIP5=ON, DIP8=OFF, DIP9=OFF)
Heating cable setpoint (ANK only)
Index - String
MIN
value
MAX
value
Parameter function
-20 °C 10 °C
Heating cable activated with an external air temperature lower than the value of this
parameter. Heating cable deactivated with an external air temperature higher than the
value of this parameter, plus 1.0° hysteresis.
Thermostat pump switch-off
01
0 = the pump continues to function when the set point temperature is reached. 1 = the
pump switches off when the set point temperature is reached (when this option is selec-
ted, the adjustment is automatically activated on the basis of the input temperature).
This parameter is only visible with the adjustment on the basis of the input temperature
(parameter (0) =1 or 2).

Other manuals for AERMEC MODUCONTROL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC MODUCONTROL and is the answer not in the manual?

AERMEC MODUCONTROL Specifications

General IconGeneral
BrandAERMEC
ModelMODUCONTROL
CategoryControl Unit
LanguageEnglish

Related product manuals