INSTALLER menu
To access the INSTALLER menu, press
the key in (Fig.9). Once the key has been
pressed, you must insert the password
to access the various menus; to access
the user menu, the password is 030.
To modify the value of the passwords,
use the arrow keys. When you have in-
serted the correct password, press the
key in (Fig.9). The monitor will show the
index of the INSTALLER parameter and
a 3-character string that identifi es it; the
string will be displayed for one second,
after which it is replaced by the value
of the parameter itself. To move on to
the next parameter, use the arrow keys
(Fig.10). To modify a parameter, just se-
lect it, press the key in (Fig.9), modify
the assigned value using the arrow keys
in (Fig.10), and confi rm the modifi cation
by pressing the key in (Fig.9) again.
R
Fig.9 Fig.10
R
Setting operational parameters (installer level)
PASSWORD = 030
Setting of input and output regulation
Index - String
MIN
value
MAX
value
Parameter function
02
The machine adjustment will depend on the value of this parameter:
• if 0, the machine adjustment is based on the output temperature;
• if 1, the machine adjustment is based on the input temperature;
• if 2, the machine adjustment is based on the temperature of the remote probe,
as read on the DHW panel (in the event of a fault on the remote probe, the machine
adjustment is based on the built-in probe, signalling this fact via alarm code 157).
If the production of hot domestic water is activated, the adjustment is automatically for-
ced on the water output temperature, regardless of the value of this parameter.
Setting cooling FORCE-OFF
Index - String
MIN
value
MAX
value
Parameter function
-25°C 25°C
The units check the working temperature (input or output), to which a safety threshold is
connected, and beyond which the compressor is switched off immediately and automati-
cally; this threshold is called FORCE-OFF.
WARNING The following parameters
must only be modifi ed by qualifi ed
personnel authorised to install the
unit.
j
j
j
Parameters only visible in heat pump models
j
j
j
Parameters only visible in models set for
hot domestic water production
Parameters only visible in the models with DCP installed
Parameters only visible in bicompressor models
Parameters only visible in the models with inverter compressor

Other manuals for AERMEC MODUCONTROL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC MODUCONTROL and is the answer not in the manual?

AERMEC MODUCONTROL Specifications

General IconGeneral
BrandAERMEC
ModelMODUCONTROL
CategoryControl Unit
LanguageEnglish

Related product manuals