49
GB
6343841_00 / Ver - 4.20
Setting of proportional cooling band
Index - String
MIN
value
MAX
value
Parameter function
1°C 20°C
This parameter indicates the proportional band applied to the cooling set; this band
produces the optimised management of the compressor, only switching it on if the inlet/
outlet water temperature (depending on the type of control set by parameter (0) in the
installer menu) is greater than the cooling work set (parameter (1) user menu) plus the
value of this parameter.
Setting of heating temperature
Index - String
MIN
value
MAX
value
Parameter function
j
j
25°C (*)
This parameter indicates the value of the work setting active in heating mode. In cooling
only units, this parameter is displayed but it cannot be modified.
(*) the maximum limit can be configured by means of the parameter (t) of the installer
menu
Setting of proportional heating band
Index - String
MIN
value
MAX
value
Parameter function
j
j
1°C 20°C
This parameter indicates the proportional band applied to the heating set; this band
produces the optimised management of the compressor, only switching it on if the inlet/
outlet water temperature (depending on the type of control set by parameter (0) in the
installer menu) is less than the heating work set (parameter (3) user menu), minus the
value of this parameter. In cooling only units, this parameter is displayed but it cannot be
modified.
Settings made on the basis of outside temperature
Index - String
MIN
value
MAX
value
Parameter function
03
This setting activates the algorithm of compensation of the work setting:
(°C)
(°C)
SET (F)
SET (H)
SET (G) SET (I)
In cooling mode, the work setting is cal-
culated automatically on the basis of the
outside temperature, following the logic
highlighted in the diagram.
(°C)
(°C)
SET (J)
SET (N)
SET (L) SET (O)
In heating mode, the work setting is cal-
culated automatically on the basis of the
outside temperature, following the logic
highlighted in the diagram.
SF1
SF2
TF1 TF2
SC1
SC2
TC1 TC2
SF1: index (6) user menu;
SF2: index (8) user menu;
TF1: index (7) user menu;
TF2: index (9) user menu;
SC1: index (A) user menu;
SC2: index (C) user menu;
TC1: index (B) user menu;
TC2: index (d) user menu;
j
j
j
Parameters only visible in heat pump models
j
j
j
Parameters only visible in models set for
hot domestic water production
Parameters only visible in the models with DCP installed
Parameters only visible in bicompressor models
Parameters only visible in the models with inverter compressor

Other manuals for AERMEC MODUCONTROL