51
GB
6343841_00 / Ver - 4.20
Setting heating set 2
Index - String
MIN
value
MAX
value
Parameter function
j
25°C (*)
This parameter indicates the minimum value of the heating setting, corresponding with
the maximum outside air temperature (index (C) user menu). This parameter is only visi-
ble if the compensation function has been activated (index (5) user menu). (*) the maxi-
mum limit can be configured by means of the parameter (t) of the installer menu
Setting the outside air temperature 2 (heating)
Index - String
MIN
value
MAX
value
Parameter function
j
-40°C 50°C
This parameter indicates the maximum outside air temperature taken into consideration
for heating compensation. This parameter is only visible if the compensation function has
been activated (index (5) user menu).
Setting domestic water temperature setpoint
Index - String
MIN
value
MAX
value
Parameter function
25°C (*)
The heat pumps have a work setting for producing domestic water; this setting indicates
the processed water temperature beyond which the compressor stops. Remember that
to visualise this setting, parameter (A) of the installer menu must be active (set value =
1). (*) the maximum limit can be configured by means of the parameter (t) of the instal-
ler menu
Setting domestic water proportional band
Index - String
MIN
value
MAX
value
Parameter function
1°C 20°C
This parameter indicates the proportional band applied to the hot domestic water set;
this band produces the optimised management of the compressor, only switching it on if
the inlet/outlet water temperature (depending on the type of control set by parameter
(0) in the installer menu) is less than the hot domestic water set (parameter (E) user
menu), minus the value of this parameter. In cooling only units, this parameter is displa-
yed but it cannot be modified.
j
Parameters only visible in heat pump models
Parameters only visible in models set for
hot domestic water production
Parameters only visible in the models with DCP installed
Parameters only visible in bicompressor models
Parameters only visible in the models with inverter compressor