Setting cooling temperature setpoint 1
Index - String
MIN
value
MAX
value
Parameter function
-20°C 26°C
This parameter indicates the maximum value of the cooling setting, corresponding with
the minimum outside air temperature (index (7) user menu). This parameter is only visi-
ble if the compensation function has been activated (index (5) user menu).
Setting the outside air temperature 1
Index - String
MIN
value
MAX
value
Parameter function
-40°C 50°C
This parameter indicates the minimum outside air temperature taken into consideration
for cooling compensation. This parameter is only visible if the compensation function has
been activated (index (5) user menu).
Setting cooling temperature setpoint 2
Index - String
MIN
value
MAX
value
Parameter function
-20°C 26°C
This parameter indicates the minimum value of the cooling setting, corresponding with
the maximum outside air temperature (index (9) user menu). This parameter is only visi-
ble if the compensation function has been activated (index (5) user menu).
Setting the outside air temperature 2
Index - String
MIN
value
MAX
value
Parameter function
-40°C 50°C
This parameter indicates the maximum outside air temperature taken into consideration
for cooling compensation. This parameter is only visible if the compensation function has
been activated (index (5) user menu).
Setting heating set 1
Index - String
MIN
value
MAX
value
Parameter function
j
25°C (*)
This parameter indicates the maximum value of the heating setting, corresponding with
the minimum outside air temperature (index (b) user menu). This parameter is only visi-
ble if the compensation function has been activated (index (5) user menu).
(*) the maximum limit can be configured by means of the parameter (t) of the installer
menu
Setting the outside air temperature 1 (heating)
Index - String
MIN
value
MAX
value
Parameter function
j
-40°C 50°C
This parameter indicates the minimum outside air temperature taken into consideration
for heating compensation. This parameter is only visible if the compensation function has
been activated (index (5) user menu).
j
Parameters only visible in models set for
hot domestic water production
Parameters only visible in the models with DCP installed
Parameters only visible in bicompressor models
Parameters only visible in the models with inverter compressor