StA
StF
bnF
StC bnC CSt SF1 tF1 SF2 tF2 SC1 tC1 SC2 tC2 SAS bAS
0 123 45 6 7 89 ABCDEF
ANL 0 7 5 45 5 0 12 18 7 30 45 0 35 18 50 10
ANLI 0 7 5 45 5 0 12 18 7 30 45 0 35 18 50 10
ANR 0 7 5 45 5 0 12 18 7 30 45 0 35 18 50 10
ANF 0 7 5 45 5 0 12 18 7 30 45 0 35 18 50 10
ANK 0 7 5 45 5 0 12 18 7 30 45 0 35 18 50 10
SRPV1
SRA
1 --- --- 65 5 0 12 18 7 30 45 0 35 18 50 10
String
index
Meaning of parameter
Contents
index
Meaning of parameter
0 - StA Selection of operational mode 8 - SF2 Cooling setpoint 2
1 - StF Cooling setpoint 9 - tF2 Outside air temperature 2 (cooling)
2 - bnF Cooling band A - SC1 Heating setpoint 1
3 - StC Heating setpoint B - tC1 Outside air temperature 1 (heating)
4 - bnC Heating band C - SC2 Heating setpoint 2
5 - CSt Setpoint correction D - tC2 Outside air temperature 2 (heating)
6 - SF1 Cooling setpoint 1 E - SAS Domestic water setpoint
7 - tF1 Outside air temperature 1 F - bAS Domestic water band
ELECTRIC HEATER menu - (Password 001)
j
Heat
recovery
unit
SrA brA Sri bri tA1 tA2 bA
0
123456
ANL 4 1 3 4 5 -30 2
ANLI 4 1 3 4 5 -30 2
ANR 4 1 3 4 5 -30 2
ANF 4 1 3 4 5 -30 2
ANK 4 1 3 4 5 -30 2
SRPV1
SRA
4 1 3 4 5 -20 2
Con-
tents
index
Meaning of parameter
Contents
index Meaning of parameter
0 - Sra Anti-freeze electric heater setpoint 4 - tA1 External air temperature setpoint 1
1 - brA Anti-freeze electric heater band 5 - tA2 External air temperature setpoint 2
2 - Sri Supplementary electric heater setpoint 6 - bA Band on air temperature setpoints
3 - bri Supplementary electric heater band
j
Parameters only visible in heat pump models
Parameters only visible in models producing hot domestic water
ELECTRIC HEATER default settings