AIREDALE ET05D - Troubleshooting Guide; Common Unit Operation Faults

AIREDALE ET05D
90 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Ecotel™ Telecoms
80
Ecotel™ 5-15kW Technical Manual 9321381 V1.3.0 02_2018
Troubleshootng
Troubleshooting
FAULT POSSIBLE CAUSE REMEDY/ACTION
Unit not operating -
Power Off.
Main/local isolator off Check all isolators from mains to unit.
Mains Fuse(s) failed.
Check all mains fuses. Replace after
correcting fault. Check for loose wire.
Unit not operating -
Power On.
Fault Alarm
Check volt free contacts, investigate and
clear fault.
Fire detection or external interlock fault
no feed on wire.
Investigate and correct.
Control MCB tripped.
Re-set after investigating and correcting
fault.
Loose wire in control circuit Investigate and tighten connector.
Motor/Fan Assembly jammed.
Isolate unit and check free rotation of motor/
fan assembly. If faulty - replace.
Fan internal protection tripped.
Investigate internal protection, which is self-
resetting. Check fan for correct operation.
Replace if faulty.
Faulty motor windings/capacitor.
Motor humming would indicate fault in motor
or capacitor.
Safety device or internal relay switch
open circuit.
Check through circuitry starting at control
MCB - action faults. Check primary and
secondary voltage.
Anti cycling timer.
Wait until timer times out and try again.
Limited to 10 starts/hour.
Unit operating -
No Cooling/Heating
Overheat cut-out operation (optional)
If auto reset has tripped – heaters will reset
automatically – Check fan and lters for
sufcient airow.
If manual reset has tripped – heaters can
only be reset manually - Check fan and
lters for sufcient airow.
Loose connection in control circuit. Check and tighten connections.