Technical Data - Chilled Water
Performance Data - (C0)
Part Load - (C0)
Water Temperatures (°C)
Air On DB / RH 10/16 11/17 12/18 13/19 14/20
LIR6042U-C045
25°C / 42%
Gross Total Cooling (kW)
14.52 13.66 12.81 11.62 9.78
Power Input (kW)
0.15 0.15 0.15 0.15 0.15
EER
96.80 91.07 85.40 77.47 65.20
30°C / 32%
Gross Total Cooling (kW)
20.62 19.03 17.58 16.44 15.80
Power Input (kW)
0.15 0.15 0.15 0.15 0.15
EER
137.47 126.87 117.20 109.60 105.33
35°C / 24%
Gross Total Cooling (kW)
26.84 25.39 24.03 22.84 21.86
Power Input (kW)
0.15 0.15 0.15 0.15 0.15
EER
178.93 169.27 160.20 152.27 145.73
40°C / 18%
Gross Total Cooling (kW)
32.30 31.09 29.98 28.86 27.60
Power Input (kW)
0.15 0.15 0.15 0.15 0.15
EER
215.33 207.27 199.87 192.40 184.00
LIR6042U-C060
25°C / 42%
Gross Total Cooling (kW)
17.76 16.42 15.13 13.69 11.91
Power Input (kW)
0.25 0.25 0.25 0.25 0.25
EER
71.04 65.68 60.52 54.76 47.64
30°C / 32%
Gross Total Cooling (kW)
25.94 24.26 22.68 21.15 19.66
Power Input (kW)
0.25 0.25 0.25 0.25 0.25
EER
103.76 97.04 90.72 84.60 78.64
35°C / 24%
Gross Total Cooling (kW)
33.87 32.24 30.68 29.15 27.65
Power Input (kW)
0.25 0.25 0.25 0.25 0.25
EER
135.48 128.96 122.72 116.60 110.60
40°C / 18%
Gross Total Cooling (kW)
41.08 39.59 38.15 36.68 35.06
Power Input (kW)
0.25 0.25 0.25 0.25 0.25
EER
164.32 158.36 152.60 146.72 140.24
All the performance data is based on a SHR of 1.0.
Part load duty data is based on unit operating at half of maximum air volume.
Performance data is based upon a unit with no ltration.