EasyManua.ls Logo

AIREDALE LogiCool InRak - Performance Data - (CO) Part Load (Cont.)

AIREDALE LogiCool InRak
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Data - Chilled Water
Performance Data - (C0)
Part Load - (C0)
Water Temperatures (°C)
Air On DB / RH 10/16 11/17 12/18 13/19 14/20
LIR6042U-C045
25°C / 42%
Gross Total Cooling (kW)
14.52 13.66 12.81 11.62 9.78
Power Input (kW)
0.15 0.15 0.15 0.15 0.15
EER
96.80 91.07 85.40 77.47 65.20
30°C / 32%
Gross Total Cooling (kW)
20.62 19.03 17.58 16.44 15.80
Power Input (kW)
0.15 0.15 0.15 0.15 0.15
EER
137.47 126.87 117.20 109.60 105.33
35°C / 24%
Gross Total Cooling (kW)
26.84 25.39 24.03 22.84 21.86
Power Input (kW)
0.15 0.15 0.15 0.15 0.15
EER
178.93 169.27 160.20 152.27 145.73
40°C / 18%
Gross Total Cooling (kW)
32.30 31.09 29.98 28.86 27.60
Power Input (kW)
0.15 0.15 0.15 0.15 0.15
EER
215.33 207.27 199.87 192.40 184.00
LIR6042U-C060
25°C / 42%
Gross Total Cooling (kW)
17.76 16.42 15.13 13.69 11.91
Power Input (kW)
0.25 0.25 0.25 0.25 0.25
EER
71.04 65.68 60.52 54.76 47.64
30°C / 32%
Gross Total Cooling (kW)
25.94 24.26 22.68 21.15 19.66
Power Input (kW)
0.25 0.25 0.25 0.25 0.25
EER
103.76 97.04 90.72 84.60 78.64
35°C / 24%
Gross Total Cooling (kW)
33.87 32.24 30.68 29.15 27.65
Power Input (kW)
0.25 0.25 0.25 0.25 0.25
EER
135.48 128.96 122.72 116.60 110.60
40°C / 18%
Gross Total Cooling (kW)
41.08 39.59 38.15 36.68 35.06
Power Input (kW)
0.25 0.25 0.25 0.25 0.25
EER
164.32 158.36 152.60 146.72 140.24
IT Cooling
LogiCool InRak™
37
InRak™ Technical Manual 7462807 V1.11.0_04_2016
Technical
Single Circuit
(C0)
All the performance data is based on a SHR of 1.0.
Part load duty data is based on unit operating at half of maximum air volume.
Performance data is based upon a unit with no ltration.

Table of Contents

Related product manuals