26 ProHood Capture Hoods PH730/PH731
Settings
Settings menu is where you can set the general
settings. These include Language, Beeper, Select
Units, Time Constant, Contrast, Set Time, Set
Date, Time Format, Date Format, Number Format,
Backlight, Auto Off. Use the arrow keys to select
an option or to change the settings for each
option. Press the key to accept settings.
In addition to the general settings, the Settings
menu also includes RS232 Baud Rate, Deadband
and Headphone Input configuration settings.
SETTINGS
Language English
Beeper Disable
Select Units
Time Constant 1 Second
Contrast 5
Set Time 09:14 AM
Set Date 01/07/12
Time Format 12 hr
Date Format MM/DD/YY
Number Format XX,XXX.YY
Backlight Auto
Auto Off Enable
RS232 Baud Rate 9600
Deadband Enable
Headphone Input Enable
Sets the speed a computer will accept information.
The deadband determines the velocity or volume measurement threshold for
displaying 0. If the deadband is Enabled, readings below 18 fpm (0.0914 m/s)
or 18 cfm (30.58 m
3
/h, 8.49 l/s) will be displayed as 0. If the deadband is
Disabled, readings down to 0 will be displayed. The default is set to Enable.
The Headphone Input on the side of the meter can be either Enabled or
Disabled. When set to Enabled, the meter will default to Capture Hood mode
when the base switch is connected. When set to Disabled, the meter will not
respond to the base switch input.
Use the arrow keys to select an option or to change the settings for each option. Press the key to
accept settings.