Page 54
Code
Signal
Description
Possible Cause
Component to Check
Recommended Action
Device Actions
Supply
Fan
Compressor/
Cond Fan
Heat
Damper
Main power has been
lost.
Check if the main power
is OK.
Turn main power on.
The current to the fan is
higher than normal.
Check if the switch, relay
or built-in fan protection is
disconnected.
Close the switch, and check.
If the fan is defective, replace
it.
Check if the connection
to the corresponding
input terminal (ID6) is ok
or if the controller board
is defective.
Check if the connection is
ok.
Reconnect the cable.
If the controller board is
defective, replace it.
A15
A16
Dirty air filter
Alarm is reset
automatically.
The alarm is a
warning to the
replace the filter.
Filter is clogged.
Check if the filter is dirty.
Clean or replace the filter
Check if the connection
to the corresponding
input terminal (ID5) is ok
or if the controller board
is defective.
Check if the connection is
ok.
Reconnect the cable.
If the controller board is
defective, replace it.
The value set for the air
pressure diff. switch is
too low.
Check the air pressure
diff switch value.
Correct the value of the
switch to standard value.
A17
pLAN alarm
Each unit continues
to work separately. It
can be reset
automatically.
The pLAN cable is
disconnected.
Check if the cable is
connected or shorted.
Reconnect the cable.
A18
Clock card
alarm
The clock function is
not available. Both
time display function
and history alarm
record function are
disabled.
It can be reset
automatically.
Clock card is loose.
Fix the clock card on the
controller board
After the clock card is fixed,
check if the alarm is
removed.
The clock card has
failed.
After fixing the clock card,
the alarm still exists.
Replace it.
A19
Humidity
alarm
The free cooling
damper will be
closed. It can be
reset automatically.
Humidity sensor (port
J2-B3 on unit 1
controller) failure.
Check if the cable is
connected or shorted.
Replace it.
Closed
The humidity is higher
than standard value.
Dry the sensor, and then
check if the alarm is
cleared.
Relocate the sensor.
A20
Indoor temp.
sensor
defective
It can be reset
automatically.
Indoor temperature
sensor (port J2-B2 on
unit1 controller) failure.
Check if the cable is
connected or shorted.
Replace it.