EasyManua.ls Logo

Akytec PR200 - Functioning; Operating Mode; Fault Mode and Error Handling; RS485 Network Interface

Akytec PR200
45 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functioning
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
9
4 Functioning
Once the application has been transferred to the non-volatile memory, the relay restarts. On
startup the relay runs a self-test. If unsuccessful, the relay switches to the fault mode (see
4.2). Otherwise the application runs (Fig. 4.1)
WARNING
Before transferring the application to PR200 ensure that all devices connected to
the relay outputs are disconnected. It is recommended to transfer the application
before wiring the relay.
NOTICE
Before starting
Before switching on, make sure that the device was stored at the specified ambient
temperature (-20 ... +55 °C) for at least 30 minutes.
4.1 Operating mode
Operating mode of the device is cycle oriented:
Start (testing of operational readiness)
Update of the input process image
Running the application
Update of the output process image
Back to Start.
Fig. 4.1 Operating sequence
4.2 Fault mode
Table 4.1 Error messages
Indication
Cause
Remedy
LOGIC Program
INVALID
Invalid application
Repare application with ALP
LOGIC Program
MEMORY ERROR
Retain variables cannnot be
read
LOGIC Program
BLOCKED
RUN-STOP jumper is set,
application stopped (see 4.6)
Remove the RUN-STOP jumper
and restart the device
LED F2 lit
Firmware is damaged
Update firmware or contact the
service center
LED F2 blinks
LOGIC Program
STOPPED
Application stopped
Start the application using
system menu and restart the
device
4.3 RS485 network interface
PR200 can have up to two RS485 interface cards (depends on modification) for
communication via Modbus RTU / ASCII protocol as a Master or a Slave.
The interface card PR-IC485 is set to Slave by default. To use the interface as a Master,
jumpers XP4 and XP5 on the card must be set in accordance with the Fig. 4.2:
set jumpers on the interface card to the ‘M’ position
configure the interface using the ALP software (Menu>Device>Configuration)

Other manuals for Akytec PR200