Programming
5-11
Setup Group (continued)
[Maximum Fre
q
]
Parameter # 19 Factory Default 60 Hz
[Maximum
Freq]
Parameter Type Read & Write Minimum 40 Hz
This parameter sets the highest frequency the drive will
output. Important: All analog inputs to the drive (4-20mA,
0-10V, Remote Pot) are scaled for the range [Minimum
Freq] to [Maximum Freq]. Max hertz may be set to less
than base hertz.
Units 1 Hz Maximum 400 Hz
Important: This parameter can
not be programmed while the
drive is running.
[Sto
p
Select]
Parameter # 10 Factory Default ‘‘Ramp”
[Stop
Select]
Parameter Type Read & Write
This parameter selects the stopping mode when the drive
receives a valid sto
p
command.
Units Text Settings ‘‘Coast”
Causes the Drive to Turn Off
Immediately
receives
a
valid
stop
command
.
‘‘Ramp” Drive Decelerates to 0 Hz, Then Turns
Off – Requires a Value In
[Decel Time 1] or [Decel Time 2]
‘‘DC Brake”
Injects DC Braking Voltage Into the
Motor – Requires a Value in Both
[Decel Hold Time] & [Decel Hold
Level].
‘‘S-Curve”
Drive ramps to stop using ‘fixed S-Curve’
profile. Stop time is twice the selected
decel time.
[
Current Limit
]
Parameter # 36 Factory Default 150 % of Drive Rated Current
[Current
Limit]
Parameter Type Read & Write Minimum 20 % of Drive Rated Current
This parameter sets the maximum drive output current that
is allowed before current limiting occurs. Important: If a
value is programmed into the [Sec Curr Limit] parameter
then that value will be the active current limit value at
speeds above 1.5 times [Base Frequency]. See Fig. 5.5.
[Output 1 Config] and [Output 2 Config] can be set to
‘‘alarm” to indicate an overload condition exists.
Units 1 % Maximum 150% of Drive Rated Current
Important: See [Cur Lim Trip En] on page 5-40.
The Drive Rated Ouput Current is based on three phase input ratings. See page 5-13 for instructions for Single Phase Input Ratings.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1305 Series and is the answer not in the manual?

Allen-Bradley 1305 Series Specifications

General IconGeneral
Series1305
DimensionsVaries by model
WeightVaries by model
Frequency Range50-60 Hz
Control MethodVolts per Hertz
Communication InterfaceRS-485
Enclosure TypeIP20
Storage Temperature-40-70°C
Humidity5 to 95% non-condensing

Related product manuals