Remote I/O Adapter Module 7
Publication 1747-IN014C-EN-P - January 2003
Configuration Parameters
The DIP switches allow you to configure the following items:
Starting Logical Rack Number (Logical Rack) - is the 1747-ASB modules
starting logical rack number in the scanners image.
Starting Logical Group Number (Logical Group) - is the 1747-ASB
modules starting logical group number within the scanners image.
Baud Rate (Baud Rate) - is the 1747-ASB modules RIO link communication
rate. The baud rate must be the same for all adapters on the RIO link.
Primary/Complementary SLC Chassis (PRI/COMP) - determines
whether the 1747-ASB module appears to the scanner as a primary or
complementary chassis.
Adapter Image Size (IMAGE SIZE) - indicates the I/O image size to be
reserved for the adapter. It can be any size between 2 and 32 groups in
2 logical group increments.
Hold Last State (HLS) - determines whether the discrete output modules
are held in their last state when:
RIO link communication with the 1747-ASB module is lost.
The scanner inhibits the 1747-ASB module.
The scanner sends Reset, Adapter Decide commands to the 1747-ASB
module.
Processor Restart Lockout (PRL) - determines whether the 1747-ASB
module automatically resumes RIO link communications if communication is
lost and then restored.
Link Response Time (RESP) - selects restricted or unrestricted RIO link
response time.
Last Chassis/PLC-3 Backup (LAST CHA) - When the 1747-ASB module is
used with a PLC-2 or PLC-5, this switch indicates to the scanner that the
1747-ASB module is the last adapter mapped into the 1747-ASB modules
highest logical rack. When using a PLC-3 processor, the switch determines
whether the 1747-ASB module supports the PLC-3 backup function.
Addressing Mode (ADDR MODE) - determines the 1747-ASB modules
remote chassis and remote expansion chassis addressing mode. 2-slot,
1-slot, and 1/2-slot are available.
Specialty I/O Mode (SP MODE) - determines whether the 1747-ASB
module discretely maps or block transfer maps specialty I/O modules in its
remote chassis and remote expansion chassis.
I/O Module Keying (KEY) - determines if the 1747-ASB module saves its
current I/O module and DIP switch configuration to its non-volatile memory,
or if the 1747-ASB module compares the current I/O module and DIP switch
configuration to the one saved in its non-volatile memory.

Other manuals for Allen-Bradley 1747-ASB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1747-ASB and is the answer not in the manual?

Allen-Bradley 1747-ASB Specifications

General IconGeneral
BrandAllen-Bradley
Model1747-ASB
CategoryControl Unit
LanguageEnglish

Related product manuals