Chapter 3
Configure a ControlNet Module
56 Rockwell Automation Publication CNET-UM001F-EN-P - February 2018
11. From the Save Configuration dialog box, select Optimize and
rewrite the schedule for all connections.
12. Click OK.
Important:
It is better to optimize connections. However, in some cases
involving multiple controllers, the Merge changes into existing
schedule option is available. This option lets controllers whose
connections have not changed to continue uninterrupted operation.
When you merge changes into the existing schedule, those
controllers whose connections have not changed remain in Run
mode rather than changing to Program mode.
13. In the Logix Designer application, save the online project.
If you change a previously scheduled network, you must reschedule the
network to apply the changes. For example, if you add I/O to an existing
ControlNet network, you must reschedule the network for the I/O to become
active.
To reschedule an already scheduled ControlNet network, follow this
procedure in RSNetWorx for ControlNet software.
1. From the File menu, choose Open.
2. From the Open dialog box, select the ControlNet file that matches the
existing network and click Open.
Reschedule a
ControlNet Network
that has Previously
been Scheduled