EasyManua.ls Logo

Allen-Bradley 1791ES-IB8XOBV4 - Page 113

Allen-Bradley 1791ES-IB8XOBV4
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 1791ES-UM001G-EN-P - November 2016 113
Get Diagnostic Status from Modules by Using Explicit Messaging Appendix A
If any input or output status bits go to a value of 0 (0 = bad; 1 =
good), use the CombinedInputStatus and CombinedOutputStatus
bits to condition your MSG rungs as follows.
Only use of the CombinedInputStatus bit is shown. Create similar
rungs by using the CombinedOutputStatus bit instead of the
CombinedInputStatus bit.
The second rung can be used to read the status on mode transition
and once a fault is detected, continue reading until the fault is
corrected.
Place these rungs in the standard task.
Figure 45
Figure 49 show the MSG instruction parameters to read
Instance 860 from the 1732ES-IB12XOB4 module. See Appendix C
of
this manual for a layout of possible instances.
Figure 45 - Instance 860 Configuration Tab

Table of Contents

Related product manuals