Rockwell Automation Publication 2099-UM001D-EN-P - December 2012 79
Connect the Kinetix 7000 Drive System Chapter 4
Removing the Ground Jumper on 2099-BM06-S, 2099-BM07-S, and
2099-BM08-S Drives
Figure 47 shows the location of the jumpers in 2099-BM06-S, 2099-BM07-S,
and 2099-BM08-S drives on the power chassis. The common mode capacitor
jumper is indicated by callout 1 (PEA) and the MOV jumper is indicated by
callout 2 (PEB).
Remove each jumper by carefully pulling it straight out.
Figure 47 - Ground Jumper Location on 2099-BM06-S, 2099-BM07-S, and
2099-BM08-S
BR1 BR2 DC+ DC- U/T1 V/T2 W/T3 R/L1 S/L2 T/L3
PE B
PE A
75C Cu Wire
3 AWG [25MM
2
] Max.
16 IN. LBS.
1.8 N-M
} TORQUE
WIRE
STRIP
CONTROL
POWER
AUX IN
+ –
SHLD
SHLD
PE
75C Cu Wire
6 AWG [10MM
2
] Max.
BR1 BR2
12 IN. LBS.
1.4 N-M
} TORQUE
PE A
PE B
CM Cap
MOV
1
2
Important: Do not discard or replace the grounding hardware.