3-58 Programming and Parameters
INPUTS & OUTPUTS
Digital Outputs
379 [Dig Out Setpt]
Sets the digital output value from a communication device.
Example
Set [Data In B1] to “379.” The first three bits of this value will determine the setting
of [Digital Outx Sel] which should be set to “30, Param Cntl.
380
380
384
388
[Digital Out1 Sel]
(5)
[Digital Out2 Sel]
[Digital Out3 Sel]
Selects the drive status that will energize
a (CRx) output relay.
(1 )
Any relay programmed as Fault or
Alarm will energize (pick up) when
power is applied to drive and
deenergize (drop out) when a fault
or alarm exists. Relays selected for
other functions will energize only
when that condition exists and will
deenergize when condition is
removed. Refer to pages 1-18
&
1-17
.
(2)
Vector Control Option Only.
(3)
Activation level is defined in [Dig Outx
Level] below.
(4)
Vector firmware 3.001 and later.
(5)
When [TorqProve Cnfg] is set to
“Enable,” [Digital Out1 Sel] becomes
the brake control and any other
selection will be ignored.
(6)
Refer to Option Definitions on
page 3-56.
Default:
Options:
1
4
4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21-26
27
28
29
30
“Fault”
“Run”
“Run”
“Fault”
(1)
“Alarm”
(1)
“Ready”
“Run”
“Forward Run”
“Reverse Run”
“Auto Restart”
“Powerup Run”
“At Speed”
(6)
“At Freq”
(3)
“At Current”
(3)
“At Torque”
(3)
“At Temp”
(3)
“At Bus Volts”
(3)
“At PI Error”
(3)
“DC Braking”
“Curr Limit”
“Economize”
“Motor Overld”
“Power Loss”
“Input 1-6 Link”
(6)
“PI Enable”
(2)
“PI Hold”
(2)
“Drive Overload”
(2)
“Param Cntl
(4, 6)
381
385
389
382
386
390
383
002
001
003
004
218
012
137
157
147
053
048
184
379
381
385
389
[Dig Out1 Level]
[Dig Out2 Level]
[Dig Out3 Level]
Sets the relay activation level for options
10-15 in [Digital Outx Sel]. Units are
assumed to match the above selection
(i.e. “At Freq” = Hz, “At Torque” = Amps).
Default:
Min/Max:
Units:
0.0
0.0
0.0/819.2
0.1
380
File
Group
No.
Parameter Name & Description
See page 3-2 for symbol descriptions
Values
Related
Vector v3
00x 0xxxxxxxxxxxx
10 01234567891112131415
1 =Output Energized
0 =Output De-energized
x =Reserved
Bit #
Net DigOut1
Net DigOut2
Net DigOut3
Vector
Vector

Table of Contents

Other manuals for Allen-Bradley powerflex 700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley powerflex 700 and is the answer not in the manual?

Allen-Bradley powerflex 700 Specifications

General IconGeneral
SeriesPowerFlex 700
CategoryAC Drive
Input Voltage200-240V AC, 380-480V AC, 500-600V AC
EnclosureType 1
Control MethodSensorless Vector
CommunicationEtherNet/IP, ControlNet, DeviceNet, PROFIBUS DP, Modbus

Related product manuals