CALLING UP THE MACHINE STATUS
Type of heat pump Type of heat pump
Software version of the heating and heat pump
regulator
Bivalent level Bivalent level:
1 = a compressor may operate
2 = two compressors may operate
3 = additional heat generator
may operate as well
Operation mode Current operation mode:
Heating
Domestic hot water
Defros
Only for output-controlled heat pump:
Current capacity Heating output currently provided by
the output-controlled compressor.
This heating output can be used to set
the overow valve in a storage tank
integrated in series according to the
setting diagram in the unit instructions.
Capacity demand Required output for output-controlled
compressor controlled by the heating
and heat pump controller.
Software version SEC Current software version of the inverter
controller of the output-controlled heat
pump
CALLING UP ERROR MEMORIES
720
Error code (here by way of example)
04.08.08
Date of the resulting error (here by way of example)
15:17
Time of the resulting error (here by way of example)
Meaning of the error codes: page 32
NOTICE
Maximum the last ve resulting errors are displayed.
CALLING UP DISCONNECTIONS
04.08.08
Date of the disconnection (here by way of example)
17:28
Time of the disconnection (here by way of example)
hp / hp fault
Disconnection code (here by way of example)
Error hp = heat pump fault
err.inst. = system fault
m.o. 2hg = mode of operation second heat
generator
El. Sup. bl = el. sup. blockade
Defr. air. = air defrost (only L/W devices)
TPLmax = temperature limits of application
maximum
TPLmin = temperature limits of application
minimum
(in reversible LWD possible shutdown due to frost protection in
cooling mode - evaporation too long
below 0°C)
Low lim = lower limit of application
no requ. = no request
NOTICE
Maximum the last ve disconnections are displayed.