-24-
12.1 (continued)
RESET
to reset
timers &
outputs
STATUS TIMERS ACTIVE
SPEED 330 RPM
SUCTION 102.3 PSIA
DISCHARGE 200 PSIG
RESET
or press
reset to
reset
outputs
ESC
or press
esc for
fault home
screen
12.2 When a fault occurs on an analog channel 30-47 monitor, a “HIGH” or “LOW” indication will
additionally be displayed as to whether the point faulted on a high or low setpoint.
STATUS FAULT AL12
1st FAULT HIGH
CHAN 42 300 °F
HIGH DISCHARGE TEMP
A high setpoint faulted
on an analog input.
The analog value and
“HIGH” are displayed.
RESET
press
reset to
clear
fault
13.0 TEST MODE SCREENS
WARNING: TEST MODE DISARMS ALL OUTPUTS. ACTUAL FAULTS WILL DISPLAY BUT WILL
NOT TRIP THE SYSTEM ALARM AND SHUTDOWN OUTPUTS. USE MANUAL STOP
FOR EMERGENCY SHUTDOWN.
13.1 The test mode is used for testing sensors without tripping the outputs. The controller system
stays in the test mode for a preset timed period. To enter the test mode, make sure the
home screen status line says “RUNNING”, and press the TEST key on the keypad. The
status line will display “TEST xxx SEC”; xxx being the remaining test time. To test an input,
momentarily fault a sensor. The display will show the faulted point, its description and “1st
FAULT” for the first point tested. To test another point press the TEST key, this will clear the
tested sensor from the display and will refresh the test timer to its full programmed test time.