-30-
14.8 (continued)
Channel 10's input class configuration will be displayed. Each input channel 10-27 can be
either class A, B, or C. The class for analog input channels 30-45 is programmed in the
terminal program using the PC, both the high and low setpoints of these channels are
individually selectable. A diamond next to the input class letter selects that class for the
displayed channel.
To view channel 20's input class.
TENS
press
CHAN 20
INPUT CLASS A B C
92 SECONDS TIME
DELAY ON START-UP
To view the next channel number, press the NEXT key until the arrow points to the channel
number. Select another channel number by using the UNITS or UNITS keys to increase
or decrease the channel by one or use the TENS or TENS key to increase or decrease
the channel by ten and press ENTER.
Note: On DE-2500 units which are programmed using Terminal Software Version 2.0 and
above the Timer value for Class B sensors may be adjusted from the keypad. From the
display shown above press the NEXT key until the arrow points to the time in seconds. Use
UP/DOWN ARROW keys to select the desired time in seconds. Press ENTER to save the
selection.
14.9 To edit global values, select “EDIT SAFETY SHUTDOWN” from main menu. Select “EDIT
GLOBAL VALUES” from next menu.
EDIT SETPOINTS
VIEW INPUT CLASS
6EDIT GLOBAL VALUES
MORE MENUS
ENTER
press to
edit the
global
values
EDIT GLOBAL VALUES
TEST TIME 100 SEC
edit the class C global
time
To change the global time for the class C sensor inputs, use the UNITS or UNITS keys to
increase or decrease the value by one. Use the TENS or TENS keys to increase or
decrease the value by ten. Press the ENTER key to save the new value and advance to the
next value to be changed. Press the NEXT key without making a change to the class C time
to reach the test time. Pressing the NEXT key when the arrow is pointing to the node number
brings the edit pointer back up to the class C time.