SEQUENCE CHART FOR AUTO START:
EVENT OR
COMMAND [---FAULT or STOP--][ AUTO START]
ENGINE
STATUS [-----STOPPED-------][---WAITING---][--CRANKING--][--RUNNING--]
OUTPUTS
IGNITION
OUT #1 [---OFF-------------------------][5 sec][-----ON-------------]
FUEL
OUT #2 [---OFF---------------------------------][5 sec][--ON---------]
PRE-LUBE
OUT #4 [---OFF-----------][------ON---timer 0-999 sec------][--OFF--]
CRANKING
OUT #3 [---OFF---------------------------][--ON--rpm/timer][--OFF----]
RPM OUT [----------------ZERO-SPEED-------------------------][--IDLE--]
4-20 ma
CAPACITY [---------UNLOADED--------------------------------------------]
4-20 ma
LOAD [-----------------OFF-----------------------------------------]
PULSE OUT
UNLOAD [----------------ON--MAX--PULSE-WIDTH--ONCE--PER--LOOP--------]
INPUTS
CLASS A [----------------------ARMED----------------------------------]
CLASS B [--TIMERS--][--ARMED------]
CLASS C [--ARMED AS CLEARED-------]
NOTES: AUTO START IS INHIBITED BY SENSING ANY RPM ABOVE 0 RPM. AUTO
START IS ABORTED BY THE DETECTION OF ANY MONITORED FAULT. CLASS
B AND CLASS C TIMERS BEGIN AT CRANKING. A LOCAL WARN ING SIGNAL
AT THE ENGINE SITE PRIOR TO CRANKING SHOULD BE PROVIDED.