-26-
13.4 To exit the test screen, press either the ESC or RESET key. Pressing the ESC key takes the
user to the “STATUS RUNNING” home screen and does not reset the class B, C and output
timers. Pressing the RESET key takes the user to the “STATUS TIMERS ACTIVE” home
screen with the class B, C and output timers reset.
ESC
press
esc key
STATUS RUNNING
SPEED 1000 RPM
SUCTION 102.3 PSIA
DISCHARGE 200 PSIG
No sensors faulted.
Running home screen is
displayed.
RESET
press
reset key
STATUS TIMERS ACTIVE
SPEED 1000 RPM
SUCTION 102.3 PSIA
DISCHARGE 200 PSIG
No sensors faulted.
Timers active home
screen is displayed.
14.0 VIEWING OR EDITING THE CONFIGURATION USING THE MENU MODE
14.1 The menu screens can be accessed from any home screen (except test) by pressing the
MENU key. The menu screens allow the user to view or edit global values, and the time
and date. The controller must be initially configured using the terminal program running on
a PC connected to the RS-232 port on the back of the controller. Reference the
programming instructions form DE PI for instructions on how to configure the controller
system for a specific application. The menu screens are intended to view or edit the already
programmed values in the field. Changes made in the menu are stored in permanent
memory and remain fixed until changed again. Listed below are the values that can be viewed
or edited:
A. VIEW or EDIT THE GLOBAL VALUES:
1. TEST TIME - from 1 to 999 seconds.
2. NODE NUMBER - from 1 to 99 (default is 1).
3. CLASS C TIMER - from 1 to 999 minutes.
B. VIEW THE INPUT CLASS:
The input class options are:
- Class A - no time delay on start-up.
- Class B - 10 to 999 seconds time delay on start-up before input is active.
- Class C - safe-until-first-met with a global time delay.
C. VIEW or EDIT THE OUTPUT CONFIGURATION:
1. CONFIGURATION
- N/O (Normally Open) - open in the normal run state and closes upon a fault
- N/C (Normally Closed) - closed in the normal run state and opens upon a
fault or loss of 12-24 Vdc input power.
- IGN (Ignition Shorting and Fuel Valve Trip Module, Altronic P/N 691124) -
open in the normal run state and closes upon a fault or loss of 12-24 Vdc.
2. ACTIVATION DELAY TIME - from 0 to 99 seconds.
D. VIEW or EDIT THE TIME AND DATE:
1. TIME or DATE