EVAC
The ALL CALL inputs have priority over the OWS Control switches. Turning the
ALL CALL facility OFF (All Call 'CANCEL') will return the OWS to its condition before the use of the
All Call facility.
8.1.4 Buzzer
The ECP is fitted with an internal buzzer which is activated by the following conditions:
amplifier / speaker line fault
visual alarm line fault
alarm system fault (FACP, EAID)
communications fault (to other ECP’s)
system on batteries - local if locally powered, or remote if remotely powered
battery fault - local if locally powered, or remote if remotely powered
charger fail - local if locally powered, or remote if remotely powered
signal generator fail
module fault
system fault
WIP line fault
visual line fault
EAID line fault
microphone pre-amp fail
8.1.5 Buzzer Mute / Alarm Acknowledge
When the BUZZER MUTE button is pressed, all outstanding alarm and fault conditions are
acknowledged. All flashing indicators go steady, and the buzzer is muted. For system wide faults,
pressing the BUZZER MUTE at any ECP will acknowledge the fault at all ECP’s.
System wide faults are:
amplifier / speaker line fault
visual alarm line fault
alarm system fault (FACP, EAID)
communications fault
system on batteries - if all ECP’s remotely powered
battery fault - if all ECP’s remotely powered
charger fail - if all ECP’s remotely powered
signal generator fail / microphone pre-amp fail
module fault
system fault
WIP system fault
visual line fault
EAID line fault