Axpert-Eazy AC Variable Frequency Drive
6-7
6
A309
Stall Current Limit
Selection
1 1 2 1 Select stall current limit..
=1: Local
=2: Terminal
When local is selected, B301 will be effective.
When terminal is selected, stall current limit is
set by the 0-10V analog signal at Vin.
A310
Auto Start (Line
start)
1 1 3 1
= 1: OFF
= 2: ON Without Speed Search
= 3: ON With Speed Search
A401
Control Mode 5 1 8 1 Sets the motor control mode of operation.
=1: V/F Open loop Heavy duty Control
=2: V/F Close-loop Heavy duty Control
=3: Sensor-less Heavy duty Vector Control
=4: Close-loop Heavy duty Vector Control
=5: V/F Open loop Normal duty Control
=6: V/F Close-loop Normal duty Control
=7: Sensor-less Normal duty Vector Control
=8: Close-loop Normal duty Vector Control
A402
V/F Selection 1 1 3 1 Select the appropriate v/f curve.
=1: Linear Curve
=2: Square Curve
=3: Custom setting
A403
Base Frequency % 100.0 5.0 100.0 0.1 This is output frequency at which the output
voltage reaches to Base Voltage A404 and than
after remains constant. This is percentage of
Motor Frequency B104.
A404
Base Voltage % 100.0 0.1 100.0 0.1 This is the maximum output voltage available at
Base Frequency A403. This is percentage of
Motor Voltage B102.
A405
VF1 Frequency % 25.0 1.0 100.0 0.1 These parameters are used to create the
custom V/Hz profile. Three different points for
the curve can be defined to get the profile
suitable for the application.
A405 <= A406 <= A407
A408 <= A409 <= A410.
A405~A407 are percentage of A403 and
A408~A410 are percentage of A404.
A406
VF2 Frequency % 50.0 1.0 100.0 0.1
A407
VF3 Frequency % 75.0 1.0 100.0 0.1
A408
VF1 Voltage % 25.0 0.1 100.0 0.1
A409
VF2 Voltage % 50.0 0.1 100.0 0.1
A410
VF3 Voltage % 75.0 0.1 100.0 0.1