Axpert-Eazy AC Variable Frequency Drive
6-25
6
D305
DC Brake Time Sec 0.0 0.0 25.0 0.1 It is amount of time that DC braking will be
applied when stop command is issued. To
disable DC Braking operation set this parameter
to zero.
D401
Stall Current Limit % 125.0
0.0 200.0 0.1 Set the current value as a percentage of motor
rated current for normal running condition.
The default value is 155%, when heavy duty is
set.
D402
Adjustable Over
Current Level
% 300 50 300 1 Set the upper current limit as a percentage of
motor rated current for running condition. When
set to 300%, this feature is disabled.
D403
Acceleration
Current Limit
% 150 50 200 1 Set the upper current limit as a percentage of
motor rated current for Acceleration.
D404
Under Current
Level
% 0 0 90 1 Set the lower current limit as a percentage of
motor rated current for running condition.