12 Storage
C232-302-401/402/403/404-603 / C232/EN M/A23 12-1
12 Storage
Devices must be stored in a dry and clean environment. A temperature range of -25°C
to +70°C (-13°F to +158°F) must be maintained during storage (see the Chapter on
Technical Data). The relative humidity must be controlled so that neither condensation
nor ice formation will result.
If the units are stored without being connected to auxiliary voltage, then the electrolytic
capacitors in the power supply area need to be reformed every 4 years. Reform the
capacitors by connecting auxiliary voltage to the C232 for approximately 10 minutes.