7 Settings
(continued)
7-50
C232-302-401/402/403/404-603 / C232/EN M/A23
7.1.3.4 Control
Main functions
MAIN: BI active USER
221 003
Fig. 3-54
Enabling the bay interlocking function from the local control panel.
MAIN: SI active USER
221 002
Fig. 3-54
Enabling the station interlocking function from the local control panel.
MAIN: Inp.asg. fct.block.1
221 014
Fig. 3-41
MAIN: Inp.asg. fct.block.2
221 022
Definition of the binary signal that will act as function block 1 or 2.
MAIN: Op. delay fct. block
221 029
Fig. 3-41
Setting for the operate delay of the function blocks.
MAIN: Perm.No.mot.drive op
221 027
Fig. 3-56
Setting for the permissible motor drive operations within the time interval
defined at MAIN: Mon.time mot.drives.
MAIN: Mon.time mot.drives
221 026
Fig. 3-56
Setting for the monitoring time for monitoring the number of motor drives.
MAIN: Cool.time mot.drives
221 028
Fig. 3-56
Setting for the cooling time of the motors of motor-operated switchgear
units.
MAIN: Mon.time motor relay
221 060
Fig. 3-112
Setting for the monitoring time for the motor relay.