6 Local Control Panel
(continued)
6-24
C232-302-401/402/403/404-603 / C232/EN M/A23
Control Step / Description Control
Action
Display
6 Press the ENTER key. The LED indicator
will go out. The assignment has been made.
The unit will now operate with the new settings.
If no operator has been selected, the ‘OR’
operator is always
assigned automatically
when the ENTER key is pressed. There is no
automatic assignment of classes.
C
Par/Func/Glob/MAIN
Fct.assign.trip cmd.
OR #02 DIST
Trip zone 4
7 Press the ‘up’ key to exit the list at any point
in the list.
Par/Func/Glob/MAIN
Fct.assign.trip cmd.
8 If you wish to reject the new setting while
you are still entering it (LED indicator labeled
EDIT MODE is on), press the CLEAR key. The
LED indicator will go out.
C
Par/Func/Glob/MAIN
Fct.assign.trip cmd.
OR #02 DIST
Trip zone 2
Deleting a List Parameter
If ‘MAIN: Without function’ is assigned to a given item, then all the following items are
deleted. If this occurs for item #01, everything is deleted.