Training manual CLAS
Pag. 22 di 71
3.6 “SELF ADAPTIVE HEATING RESTART DELAY”
With the parameter 2 35 it is possible chose the heating restart delay type:
0: manual;
1: automatic.
MANUAL: with the parameter 2 36 it is possible set the heating restart delay between 0 and 7 min.
AUTOMATIC: the heating restart delay is calculated in base of the heating set-point temperature, see table
below:
Heating set-point
temperature
< 50°C
51-60°C
61-70°C
71-80°C
> 80°C
Restart delay
(minutes)
5
4
3
2
1