EasyManua.ls Logo

Ariston CLAS - Gas Regulations; Supply Pressure Check; Maximum Sanitary Power Check

Ariston CLAS
71 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Training manual CLAS
Pag. 40 di 71
5.3 GAS REGULATIONS
5.3.1 SUPPLY PRESSURE CHECK
5.3.2 MAXIMUM SANITARY POWER CHECK
MAXIMUM SANITARY POWER OUTLET PRESSURE
G20
G30
G31
24 kW CF
12 mbar
27,8 mbar
35,4 mbar
24 kW FF (to February 2008)
12,2 mbar
27,7 mbar
35,5 mbar
24 kW FF (from March 2008)
12,4 mbar
28,1 mbar
34,1 mbar
28 kW FF
12,9 mbar
27,7 mbar
35,8 mbar
MINIMUM SUPPLY PRESSURE
METHANE G 20
BUTHANE G 30
PROPANE G 31
17 mbar
20 mbar
25 mbar
SUPPLY PRESSURE CHECK
.
1. Loosen screw “1” (fig. A) and insert the pressure gauge fitting
pipe in the pressure intake.
2. Put the boiler on maximum operating power (hot water tap
open). The supply pressure must correspond with the one foreseen
for the type of gas for which the boiler has been prearranged (refer
to table below).
3. After checking tighten screw “1” and check the seal.
1. To check maximum power, loosen screw “2” (fig.B) and insert the
pressure gauge fitting pipe in the pressure intake.
2. Disconnect the compensation pipe of the air chamber (fig.B).
3. Start the boiler at maximum power with the flue cleaner function
(press Reset button for 5 sec.).
4. The supply pressure must correspond with the one foreseen for
the type of gas for which the boiler has been prearranged (refer to
table below). If it does not, remove the protection cap and act on
adjusting hexagon nut “3” (fig. C).
5. After checking tighten screw “2” and check the seal.
6. Reassemble the protection cap of the modulator.
7. Reconnected the compensation pipe.
Fig. A
TUBETTO DI
COMPENSAZIONE
CAMERA D’ARIA
Fig. B
Fig. C

Table of Contents

Related product manuals