Sigmadue - microPAC MP-01 - User manual
6
2-2-2 Connector “A” connections
The “
A
” terminal block allows the connection of the +24V Power Supply, Run/Stop
,
4 Digital Inputs and 4 Digital Outputs Signals.
The terminals are positioned as follows:
1 RS
Run/Stop terminal, connecting this terminal to a 24V source, it is possible
to launch or stop the execution of the 1131 program loaded in the CPU;
2...5 1...4 4 Digital Inputs terminals
, connecting this terminal to a 24V source, it is
possible to change the status of the input;
6...9 1...4 4 Digital Outputs terminals
. Each source type (PNP) digital output can
manage a 24V 0.5A load;
10...11 L+ 24Vdc power supply terminals.
2-2-3 Connector “B” connections
The “B” terminal block allows the connection of the 0V Power Supply, 4 Digital
Inputs, 4 Digital Outputs Signals and the system hearth.
The terminals are positioned as follows:
1 M- 0V power supply terminal.
2...5 5...8 4 Digital Inputs terminals
, connecting this terminal to a 24V source, it is
possible to change the status of the input
6...9 5...8 4 Digital Outputs terminals
. Each source type (PNP) digital output can
manage a 24V 0.5A load.
10 Frame ground.
11 M- 0V power supply terminal.
Pin 1 234567891011
Label RS 1 2 3 4 1 2 3 4 L+ L+
Function Run/Stop DI1 DI2 DI3 DI4 DO1 DO2 DO3 DO4 POWER
Signal INPUT INPUT INPUT INPUT INPUT OUT OUT OUT OUT +24V +24V
Power Supply
Digital Output
Digital Input
Run/Stop
Digital Input
Pin 1 2 3 4 5 6 7 8 9 10 11
Label M- 5 6 7 8 5 6 7 8 M-
Function POWER DI1 DI2 DI3 DI4 DO1 DO2 DO3 DO4 Ground
POWER
Signal 0V INPUT INPUT INPUT INPUT OUT OUT OUT OUT Ground 0V
PowerDigital OutputDigital InputPower Frame
supply ground supply