Chapter 3 - CPU setup
13
3-2-5 Startup Setup Menu
Figure 3.6 - Startup Setup Menu
3-2-6 Persistency Setup Menu
Figure 3.7 - Pesistency Setup Menu
The CPU is able to save a PLC program in persistent memory. This means that when
PLC Program Persistency is ENABLED, the program will be automatically loaded and
executed at start-up. Every time the user downloads
a new program to the CPU
(
during the development activities),
it is saved in the persistent memory and at next
device start up, the last downloaded program will be executed. Saving a program in
persistent memory is a time consuming activity. For that reason the user may want to
disable the automatic program save to make development activities more efficient. It
can be useful to prevent execution of any program at start-up. Selecting the item
“
Erase PLC program
” the retentive memory area reserved to store PLC programs is
erased. This activity take several seconds. When the “
Persistency setup menu
”
screen reappears then the memory has been erased.
Startup Timeout The time available to enter in the startup session
Inactivity Timeout Inactivity Timeout (please see
3-1-3
for details)
Post Startup Run
After the startup session could be run the PLC program
or the I/O Watching window (1 = PLC, 2 = I/O Watch)
DO1 used by
watchdog
If enabled, the digital output DO1 could be connected to
a software function block to signal a watchdog event
DI[1...8] Counter Enable
A counter function can be enabled for each digital input
(0 = counter disabled, 1 = counter enabled)
Exit Return to previous menu
STARTUP TIMEOUT SETUP
1. Startup Timeout (2..120s): 10
2. Inactivity Timeout (2..120s): 30
3. Post Startup Run (1..2): PLC
4. DO1 used for watchdog (0..1): Disabled
5. DI[1..8] Counter Enable: 00000000
6. Exit
Enter Selection:
Ascon S.p.a.
Sigma microPAC Control Unit MP-01
Device configuration
Erase PLC Program
Command to erase the resident PLC program in the
non volatile memory
PLC Program
Persistency
If enabled every new download of a valid PLC program
will be stored in the non volatile memory
Exit Return to previous menu
PERSISTENCY SETUP
1. Erase PLC Program
2. PLC Program Persistency (0..1): ENABLED
3. Exit
Enter Selection:
Ascon S.p.a.
Sigma microPAC Control Unit MP-01
Device configuration