28
Display Parameter Available Selections
A1..AA
Output 1 Alarm Action
OFF
LAt to select latching alarm
Eunt to select an event.
nor to select normal alarm
A1..A0
Output 1 Alarm Operation
Pro.L - to select Process Low
Pro.H to select Process high
inb to select inverse band
nor.b to select normal band
dE.L to select deviation low
dE.H to select deviation high
A1..dL
Output 1 Alarm Delay* Set between 0 and 9999 seconds
A1.1H
Output 1 Alarm Inhibit** Set between 0 and 9999 seconds.
A1..SP
Output 1 Alarm Setpoint Set the alarm setpoint or “ranges” for deviation/ inverse// normal alarms.
A2..AA
Output 2 Alarm Action
OFF
LAt to select latching alarm
Eunt to select an event
nor to select normal alarm
A2..A0
Output 2 Alarm Operation
Pro.L - to select Process Low
Pro.H to select Process high
inb to select inverse band
nor.b to select normal band
dE.L to select deviation low
dE.H to select deviation high
A2.dl
Output 2 Alarm Delay* Set between 0 and 9999 seconds
A2..IH
Output 2 Alarm Inhibit ** Set between 0 and 9999 seconds.
A2..sP
Output 2 Alarm Setpoint Set the span of the sensor
Alr
A1..AA