6.
Press Edit.
Display indicates: Specialist (4)
User login
7.
Use Up Down to select user:
Information: Required user level: Specialist (4) or higher
The symbols have the following meaning:
-
black triangle: = current setting
-
white triangle: = selection (not saved yet)
8.
Press Ok.
Display indicates: Password 0***
9.
Enter password ( enter password).
The screen indicates the pre-set type of seating (▶Limit or ▶Torque) by means
of a black triangle .
Change settings
10.
Use Up Down to select new setting.
The symbols have the following meaning:
-
black triangle: = current setting
-
white triangle: = selection (not saved yet)
11.
Confirm selection via Save.
The setting for the type of seating is complete.
12.
Back to step 4 (CLOSED or OPEN): Press Esc.
10.2. Fieldbus address (slave address), baud rate, parity and monitoring time: set
Customer settings M0041
Modbus M0341
MD1 slave address M0247
MD2 slave address M0409
Baud rate M0343
Parity/stop bit M0782
Monitoring time M0781
Default values:
MD1 slave address = 247
MD2 slave address = 247
Baud rate = Auto
Parity/stop bit = Even, 1 stop bit
Monitoring time = 15 seconds
Information
Parameter MD2 slave address is only available if AUMA redundancy I (option) is
available.
For further settings and information e.g. on redundancy, refer to Manual (Device
integration).
10.3. Open switch compartment
The switch compartment must be opened to perform the following settings.
Ignition of potentially explosive atmospheres caused by sparks.
Risk of death or serious injury.
Before opening the flameproof enclosure, ensure absence of gas and voltage.
Handle cover and housing parts with care.
Joint surfaces must not be damaged or soiled in any way.
Do not jam cover during fitting.
67
SAEx 07.2 SAEx 16.2/SAREx 07.2 SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive Modbus RTU Commissioning (basic settings)

Table of Contents

Other manuals for AUMA SAEx 07.2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA SAEx 07.2 and is the answer not in the manual?

AUMA SAEx 07.2 Specifications

General IconGeneral
BrandAUMA
ModelSAEx 07.2
CategoryController
LanguageEnglish

Related product manuals