8. Signals
8.1. Feedback signals (binary)
Information The switches can be provided as single switches (1NC and 1 NO), as tandem
switches (2 NC and 2 NO) or as triple switches (3 NC and 3 NO).The precise version
is indicated in the terminal plan or on the order-related technical data sheet.
Type and designation in wiring diagramFeedback signal
Signalling via limit switches (NO), non potential-free
Value of the output signal depends on control voltage (refer to wiring diagram)
End position OPEN/CLOSED
reached
Limit switch, closing, clockwise rotationLSC
Limit switch, opening, counterclockwise rotationLSO
Option: Tandem switch with additional potential-free contacts LSC1 and LSO1
Potential-free signal via switches (NC/NO)
Condition: DUO limit switching in the actuator
Intermediate position reached
(option)
DUO limit switch, clockwise rotationLSA
DUO limit switch, counterclockwise rotationLSB
Potential-free signal via contacts, terminals XK 15 and XK 16
Condition: Relay board A5 within the controls
Output contact XK 15 closed = no torque fault
Output contact XK 16 = torque fault, i.e. the set torque was exceeded before reaching an
end position.
Torque o.k./
Torque fault
Potential-free signal via switches (NC/NO)
Condition: Torque switch in tandem arrangement with TSC/TSO
Torque OPEN/CLOSED
reached (option)
Torque switch, closing, clockwise rotationTSC1
Torque switch, opening, counterclockwise rotationTSO 1
Potential-free signal via contacts, terminal XK 13
Condition: Relay board A5 within the controls
Thermoswitch tripped (NO contact) = Output contact closed
Motor protection tripped (op-
tion)
ThermoswitchesF1, Th
Thermal overload relayF7
Potential-free signal via switches (2 x NC)
Condition: Selector switch with 2 levels
indicates selector switch position LOCAL/REMOTE
Selector switch position (op-
tion)
Potential-free signal via switch (NC)
Contact opens and closes (blinks) during an actuator operation
Running indication (option)
Blinker transmitterS5, BL
8.2. Feedback signals (analogue)
Type and designation in wiring diagramFeedback signal
Depending on version either with potentiometer or electronic position transmitter EWG/RWGValve position (option)
PotentiometerR2
Potentiometer in tandem arrangement (option)R2/2
3-wire or 4-wire system (0/4 20 mA)B1/B2,
EWG/RWG
2-wire system (4 20 mA)B3/B4,
EWG/RWG
24
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2
Signals AMB 01.1