6. If you override the tripping point inadvertently (ratchet click is heard after the
pointer has snapped): Continue turning the setting spindle in the same direction
and repeat setting process.
9.6. Test run
Perform test run only once all settings previously described have been performed.
9.6.1. Direction of rotation: check
Valve damage due to incorrect direction of rotation!
→
If the direction of rotation is wrong, switch off immediately (press STOP).
→
Eliminate cause, i.e. correct phase sequence for cable set wall bracket.
→
Repeat test run.
1. Move actuator manually to intermediate position or to sufficient distance from
end position.
2. Set selector switch to position Local control (LOCAL).
3. Switch on actuator in direction CLOSE and observe the direction of rotation on
the indicator disc.
→
Switch off before reaching the end position.
➥
The direction of rotation is correct if actuator runs in direction CLOSE and
indicator disc turns counterclockwise.
9.6.2. Limit switching: check
1. Set selector switch to position Local control (LOCAL).
31
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AMB 01.1 Commissioning (basic settings)