13.2. Technical data Actuator controls
Features and functions
Refer to name plates at controls and motor
Permissible variation of the mains voltage: ±10 %
Permissible variation of the mains frequency: ±5 %
Current consumption of controls depending on mains voltage:
100 to 120 V AC = max. 575 mA
208 to 240 V AC = max. 275 mA
380 to 690 V AC = max. 160 mA
Mains voltage, mains frequency
Category III according to IEC 60364-4-443Overvoltage category
The controls are designed for the rated motor power, refer to motor name plateRated power
Reversing contactors (mechanically and electrically interlocked) for AUMA power
classes A1/A2
Standard:Switchgear
Reversing contactors (mechanically and electrically interlocked) for AUMA power
classes A1/A2 with additional contacts, 1 NC + 1 NO each
Options:
Reversing contactors (mechanically and electrically interlocked) for AUMA power
class A3
Reversing contactors are designed for a lifetime of 2 million starts.
For the assignment of AUMA power classes, please refer to Electrical data Multi-turn actuat-
ors/Part-turn actuators.
Control inputs OPEN - STOP - CLOSE, 230 V AC, internally supplied (non po-
tential-free)
EMERGENCY-STOP function from control room, independent of position of
selector switch
Standard:Control
Control inputs , OPEN - STOP - CLOSE, 24 V DC, externally supplied (with
galvanic isolation via contact), current consumption: approx. 15 mA per input
Control inputs OPEN - STOP - CLOSE, 24 V DC, internally supplied (non poten-
tial-free)
Control inputs OPEN - STOP - CLOSE, 115 V AC, internally supplied (non po-
tential-free)
Option:
Output signals for end positions OPEN/CLOSED, 230 V AC, internally supplied
(non potential-free) for external indication lights OPEN/CLOSE (P
max
= 2.5 W)
Standard:Status signals
●
5 potential-free output signals with one common, max. 250 V AC, 2 A (res-
istive load)
-
Motor protection tripped (thermal fault)
-
Torque fault
-
No torque fault
●
Selector switch position LOCAL/REMOTE
Options:
230 V AC ±10 %, max. 2.5 W for supply of the control inputs., galvanically isol-
ated from internal voltage supply
Standard:Voltage output
24 V DC ±5 %, max. 10 mA for supply of the control inputs, galvanically isolated
from internal voltage supply
115 V AC ±10 %, max. 30 mA for supply of the control inputs, galvanically isol-
ated from internal voltage supply
Option:
Selector switch LOCAL - OFF - REMOTE (lockable in all three positions)Standard:Local controls
Push buttons OPEN, STOP, CLOSE
2 indication lights: End position CLOSED (yellow), end position OPEN (green)
3 indication lights: End position CLOSED (yellow), collective fault signal (red),
end position OPEN (green)
Options:
Special colours for the indication lights
Protection cover, lockable
53
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AMB 01.1 Technical data