Set type of seating via toggle switch [S9].
Figure 27: Signal and control board
[S9] Toggle switch
in position = limit seating
in position = torque seating
10.3. Push-to-run operation or self-retaining: set
The operation behaviour for operation commands (OPEN, STOP, CLOSE) can be
set separately via the push buttons on the local controls or for operation commands
from Remote.
Push-to-run operation
Actuator only runs in directions OPEN or CLOSE while an operation command is
being received.The actuator stops if the operation command is cancelled.
Self-retaining
After an operation command, the actuator continues to run in directions OPEN or
CLOSE, even if the operation command is cancelled (self-retaining). The actuator
is either stopped by the STOP command or if an end position or intermediate position
has been reached.
10.3.1. Push-to-run operation or self-retaining for operation commands via push buttons
Push-to-run operation or self-retaining for operation commands is set in the factory
and usually remains unchanged. Subsequent modification is however possible but
by interrupting or soldering a link on the signal and control board.
Figure 28: Signal and control board
[B3] Soldering link closed = self-retaining LOCAL
[B3] Soldering link interrupted = push-to-run operation LOCAL
10.3.2. Push-to-run operation or self-retaining for operation commands from Remote
The settings for push-to-run operation or self-retaining from Remote is made via a
jumper on the wiring board.
39
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AMB 01.1 Commissioning – controls settings