EasyManua.ls Logo

AUMA SQ 12.2 - Torque Indication and Units; Operation Commands and Setpoints

AUMA SQ 12.2
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 32: Relay board; left: version B02, right: version B04
Table 11: Feedback signals setting
LinkSignal at termin-
al
Function
(Signal at terminal XK
1)
active, if function matches)
XK 16Torque switch tripped in mid-travel and/or
Thermoswitch or thermal overload relay tripped
XK 15No torque switch tripped in mid-travel
XK 13No thermoswitch or no thermal overload relay tripped
XK 16Torque switch tripped in mid-travel
XK 15No torque switch tripped in mid-travel
XK 13No function
XK 16Torque switch tripped in mid-travel
XK 15No torque switch tripped in mid-travel
XK 13No thermoswitch or no thermal overload relay tripped
XK 16Torque switch tripped in mid-travel
XK 15No torque switch tripped in mid-travel
XK 13Thermoswitch or thermal overload relay tripped
XK 16Torque switch tripped in mid-travel
XK 15No torque switch tripped in mid-travel
XK 13No function
XK 14Common connection
refer to order-related wiring diagram BSP 1)
10.7. EMERGENCY command (EMERGENCY - OPEN/EMERGENCY - CLOSE): set
(Option)
EMERGENCY behaviour
In case an EMERGENCY command is issued, the actuator will run to the defined
end position:
For setting EMERGENCY - CLOSE: Actuator runs to end position CLOSED.
For setting EMERGENCY - OPEN: Actuator runs to end position OPEN.
The EMERGENCY command is effective for all three selector switch positions
(LOCAL, OFF, REMOTE).
Connection
The EMERGENCY command is initiated by a signal at the ESD COMMAND input
(refer to wiring diagram).
The ESD COMMAND input must be connected via an NC contact to the control voltage
(quiescent current principle). If an EMERGENCY command is issued (signal is
cancelled = NO contact activated), the actuator runs to the defined end position.