3. If the valve end position is not reached:
→
Slightly turn setting screw [2] counterclockwise until valve end position
OPEN can be safely set.
➥
Turning the setting screw [2] clockwise results in a smaller swing angle.
➥
Turning the setting screw [2] counterclockwise results in a larger swing
angle.
4. Turn setting screw [2] clockwise to the stop.
➥
This completes the setting of end stop OPEN.
5. Check O-ring in screw plug and replace if damaged.
6. Fasten and tighten screw plug [1].
Having completed this procedure, the end position detection OPEN can be set
immediately.
9.2. Switch compartment: open
The switch compartment must be opened to perform the following settings (options).
1. Loosen screws [2] and remove cover [1] from the switch compartment.
2. If indicator disc [3] is available:
Remove indicator disc [3] using a spanner (as lever).
Information: To avoid damage to paint finish, use spanner in combination with
soft object, e.g. fabric.
9.3. Torque switching: set
Once the set torque is reached, the torque switches will be tripped (overload protection
of the valve).
27
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AMB 01.1 Commissioning (basic settings)