2. Operate actuator using push buttons OPEN - STOP - CLOSE.
The limit switching is set correctly if (default indication):
- the yellow indication light is illuminated in end position CLOSED
- the green indication light is illuminated in end position OPEN
- the indication lights go out after travelling into the opposite direction.
The limit switching is set incorrectly if:
- the actuator comes to a standstill before reaching the end position
- the red indication light is illuminated (torque fault).
3. If the end position setting is incorrect: Reset limit switching.
4. If the end position setting is correct and no options (e.g. potentiometer, position
transmitter) are available: Close switch compartment.
9.7. Electronic position transmitter EWG 01.1
Option
The electronic position transmitter EWG 01.1 signals the remote position or the valve
position. On the basis of the actual valve position sensed by hall sensor, a current
signal between 0 20 mA or 4 20 mA is generated.
Technical data
Table 7: EWG 01.1
2-wire system3-wire or 4-wire systemData
4 20 mA0 20 mA, 4 20 mAOutput current I
a
24 V DC (18 32 V)24 V DC (18 32 V)Power supply U
V
1)
20 mALED off = 26 mA, LED on = 27
mA
Max. current consumption
(U
V
12 V)/20 mA
600 Ω
Max. load R
B
0.1 %Impact of power supply
0.1 %Load influence
< 0.1 /KTemperature impact
60 °C to +80 °CAmbient temperature
2)
Power supply possible via: AC, AM controls or external power supply1)
Depending on temperature range of the actuator: Refer to name plate2)
Setting elements
The EWG is housed in the actuator switch compartment. The switch compartment
must be opened to perform any settings. Refer to <Switch compartment: open>.
All settings are made via the two push buttons [S1] and [S2].
Figure 24: View on control unit when switch compartment is open
[S1] Push button: Set 0/4 mA
[S2] Push button: Set 20 mA
LED Optical aid for setting
[1] Measuring point (+) 0/4 20 mA
[2] Measuring point () 0/4 20 mA
32
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2
Commissioning (basic settings) AMB 01.1