1. Loosen all 3 screws [2] on the signal and control board [1] and remove board.
Information: Make sure not to disconnect the jumpers.
Figure 29: Remove signal and control board
2. Set push-to-run operation or self-retaining via red jumper on wiring board.
Link via B1 = self-retaining REMOTE
Link via B2 = push-to-run operation REMOTE (continuous signal RE-
MOTE)
Figure 30: Wiring board
3. Fasten signal and control board [2] again.
10.4. Local controls: mount
1. Clean sealing faces of housing and cover.
2. Check whether O-ring [3] is in good condition, replace if damaged.
3. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
Figure 31:
4. Fit local controls [1].
40
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2
Commissioning controls settings AMB 01.1