Figure 5.2.1.ii Expansion Option 36.2
The available settings for expansion option 36.2 are:
0. Disabled
Bottom blowdown time reduction is disabled.
1. Enabled, Minimum Blowdown Enforced
Bottom blowdown timing is adjusted according to the boiler’s steam production. If there is no
steam contribution, a minimum blowdown time set in expansion option 36.3 may be set to avoid
missed blowdowns.
2. Enabled, Minimum Blowdown Not Enforced
Bottom blowdown timing is adjusted according to the boiler’s steam production. If there is no
steam contribution, no blowdown will take place.
5 Bottom Blowdown
Page 72
Mk7 Manual: Expansion Board Set-Up Guide
October 2014