2.3 Commissioning Water Level
2.3.1 Commissioning Procedure
When commissioning a burner with Autoflame water level cotnrol, the water level probes must be
commissioned initially before the combustion curve is put in. Once the burner is commissioned with the
Mk7 M.M., the water level probes will need to be recommissioned once the boiler is up to pressure,
and water in the boiler is hot enough. If the water level control is optioned, the M.M. will be in error
and cannot be commissioned until the probes have been set-up.
Go into Commission mode when the system starts up and enter the password.
Figure 2.3.1.i Password Screen
2 Set-Up
Page 20
Mk7 Manual: Expansion Board Set-Up Guide
October 2014