BCM50 Hardware & Installation
18 NN40011-002 Issue 1.2 BCM50 Rls 6.0
Environment Checklist
The installation area must be:
Minimum of 4 m (13 ft) from equipment such as photocopiers,
electrical motors and other equipment that produces
electromagnetic, radio frequency and electrostatic interference
Within 1.5 m (5 ft.) of a three-wire grounded electrical outlet
Clean, free of traffic and excess dust, dry and well ventilated
Within the temperature ranges of 0°C and 40°C (32°F and 95°F)
Between 20% and 80% non-condensing relative humidity
Enough space and strength to support the BCM base unit
Minimum of 46 cm (18 in.) from the floor
Note: The installation area must be of sufficient height from the floor to
prevent water damage.
You also need the following equipment to install a BCM50 unit:
mounting hardware (either a rackmount shelf, a wallmount bracket
per unit or four rubber feet per unit)
Phillips screwdriver #2
flat blade screwdriver
pliers
antistatic grounding strap
connecting tool
surge protector (recommended)
cables, 25-pair cable with RJ-21 connectors