6-15
Chapter 6. SETTINGS DURING OPERATION
rE-1 (Manual reset) setup
(1) In the operation display mode, keep the [para] key
pressed for 2 s or longer.
>>
The unit then enters the parameter setting mode.
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
(2) Press the [para] key several times.
>>
Display the parameter setting [rE-1: Manual
reset].
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
(3) Press the [
], or [
] key to change the set value in
[[rE-1].
Setting range: -10.0 to +110.0%
>>
When no keys are pressed for 2 s or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(4) Press the [mode] key.
>>
The display is returned to the operation display.
Handling Precautions
• When [CtrL: Control method] is set at [0: ON/OFF control], [rE-1] is not
displayed.
• When [C26: Heat/Cool control] is set at [0: disabled] and [I-1: Integration
time] is set at a value other than “0”, [rE-1] is not displayed.
• When [C26: Heat/Cool control] is set at [1: enabled] and both [I-1:
Integration time] and [I-1c: Cool-side integration time] are set at a value
other than “0”, [rE-1] is not displayed.