4-11
Chapter 4. WIRING
Contact the thermocouple wires to the terminals in case of a thermocouple input. When a thermocouple is
connected to terminals, or wiring distance is long, connect the wire via a shielded compensating lead wire.
For input/output other than thermocouples, use a JCS 4364 instrument cable or
equivalent (generally called twisted shielded cable for instrumentation use).
Recommended twisted shielded cables.
Fujikura Ltd. 2 conductors IPEV-S-0.9 mm
2
× 1P
3 conductors ITEV-S-0.9 mm
2
× 1T
Hitachi Metals, Ltd.
2 conductors KPEV-S-0.9 mm
2
× 1P
3 conductors KTEV-S-0.9 mm
2
× 1T
A shielded multiconductor microphone cord (MVVS) may be used, if
electromagnetic induction noise are comparatively low.