Chapter 6. SETTINGS DURING OPERATION
PV filter setup
The PV filter (primary filter with the software) is activated to remove the noise
from the PV input.
(1) In the operation display mode, keep the [para] key
pressed for 2 s or longer.
>>
The unit then enters the parameter setting mode.
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
(2) Press the [para] key several times.
>>
Display the parameter setting [FL: PV filter].
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
(3) Press the [<], [
], or [
] key to change the set value
in [FL].
Setting range: 0.0 to 120.0 s
>>
When no keys are pressed for 2 s or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(4) Press the [mode] key.
>>
The display is returned to the operation display.